Eversolar Eversol Solar InverterFor an Eversolar Eversol Solar Inverter, performing a proper shutdown procedure can already fix some minor issues. But there are some errors that involve doing some specific steps. Gold Coast Power Solutions have put together a list of faults, displays and possible actions in case you experience any of the problems below.

As a tip, you will recognize a fault on an Eversolar Eversol Solar Inverter by the red LED that will light up instead of the green LED. It will also show one of the LCD display messages below.

View the Eversolar Eversol Solar Inverter user manual here.

Need service for your solar power system?

Fault

LCD Display

Possible actions

Resumable Fault Isolation Fault 1. Check the impedance is between PV (+) & PV
(-) and the PV-Inverter is earthed. The impedance must be greater than 2MΩ
2. If the problem persists please call service
Ground I Fault 1. The ground current is too high.
2. Unplug the inputs from the PV generator and
check the peripheral AC system
3. After the cause is cleared, re-plug the PV panel and check PV-Inverter status.
4. If the problem persists please call service.
Grid Fault
Fac Over Range
Vac Over Range
1. Wait for 5 minutes, if the grid returns to normal, PV-Inverter automatically restarts.
2. Make sure grid voltage and frequency meet the specifications
3. If the problem persists please call service
Utility Loss 1. Grid is not connected.
2. Check grid connection cables.
3. Check grid usability. 4. If grid is ok, and the problem persists, maybe the fuse in the inverter is open, please call service.
Over Temperature 1. The internal temperature is higher than
specified normal value
2. Find a way to reduce the ambient temperature.
3. Or is move the inverter to a cooler environment
4. If it not effective, call local service
PV over Voltage 1. Check the open PV voltage, see if it is greater than or too close to 500VDC
2. If PV voltage is less than 500VDC, and the
problem still occurs, please call local service
Permanent Fault Consistent Fault 1. Disconnect PV (+) or PV (-) from the input,
restart the PV-Inverter
2. If it does not work, call service
Relay Failure
DC INJ High
EEPROM R/W Fail
SCI Failure
AC HCT Fault
GFCI Failure
1. Disconnect ALL PV (+) or PV (-)
2. Wait for few seconds
3. After the LCD switches off, reconnect and
check again
4. If the message reappears, please contact
local service

Need service for your solar power system?

Eversolar Eversol Solar InverterThe full details are available in the Eversolar Eversol Solar Inverter manual’s Troubleshooting section. If the issue continues after following the actions above, check if your Eversolar Eversol Solar Inverter is still within the 5-year warranty period so the issue can be covered. However, if the inverter is outside warranty, we suggest you contact a professional solar power expert. If you’re in the Gold Coast or Brisbane area contact Gold Coast Power Solutions here so our team can provide you with further assistance.

View the Eversolar Eversol Solar Inverter user manual here.

Need a quality solar inverter? We deliver Australia wide
Got A Question About Solar Power? Click Here For Answers!

Learn more about solar power battery storage here