When a Fronius inverter has a fault it usually comes up with a STATE code to explain what’s wrong; the following table lists the Fronius Galvo series inverter STATE codes so you can get an idea on what your Fronius Galvo inverter is trying to tell you and what you can do about it.
Fronius Galvo Inverter STATE codes
Looking for a Fronius IG inverter State Code? Click Here.
Looking for a Fronius Primo State Code? Click Here.
Looking for a Fronius SYMO State Code? Click Here.
Fronius STATE codes beginning with 1xx
Fronius STATE codes beginning with 1 usually only occur momentarily and are caused by the power from the street (the grid) being outside the inverters operating parameters. The Fronius inverter reacts by disconnecting from the grid and attempts to switch on again after the specified mains monitoring period, as long as no further errors occur during this period. The STATE code is displayed whilst the grid is being checked.
Code |
Description |
Behaviour |
Remedy |
STATE 102 | AC voltage too high | Following careful testing and when the grid conditions are within the permissible range again, the inverter will resume feeding energy into the grid. | Check grid connections: If this STATE code keeps recurring contact your solar power system installer. |
STATE 103 | AC voltage too low | ||
STATE 105 | AC frequency too high | ||
STATE 106 | AC frequency too low | ||
STATE 107 | AC grid outside the permissible limits | ||
STATE 108 | Stand alone operation detected |
Fronius STATE codes beginning with 3xx
Fronius Galvo STATE codes beginning with 3 are status codes that may occur while feeding energy into the grid, but generally do not cause the process to be interrupted for any length of time.
The inverter disconnects automatically from the grid, the grid is then monitored as specified and the inverter attempts to resume feeding energy into the grid.
Code |
Description |
Behaviour |
Remedy |
STATE 301 | Overcurrent (AC) | Short-term interruption while feeding energy into the grid due to over current in the inverter. The inverter resumes with its startup routine. |
Fault is rectified automatically; if this STATE code is displayed all the time: notify your local Fronius service partner. |
STATE 302 | Safety circuit detects a current peak on the PV generator side | ||
STATE 303 | Power stage set over temperature | Short term interruption while feeding energy into the grid due to over temperature. The inverter resumes with its startup routine. |
Purge openings for cooling air and heat sink if necessary; fault is rectified automatically; if this STATE code keeps recurring contact your solar power system installer. |
STATE 304 | Internal temperature too high | ||
STATE 306 | LOW PV OUTPUT Intermediate circuit voltage too low for feeding energy into the grid |
Short term interruption while feeding energy into the grid. The inverter resumes with its startup routine. |
Fault is rectified automatically; if this STATE code occurs when there is sufficient insolation (sunlight) contact your solar power system installer. IMPORTANT! Due to the low level of insolation (sunlight) early in the morning and in the evening, the STATE codes 306 (LOW PV OUTPUT) and 307 LOW PV VOLTAGE) are displayed routinely at these times of day. These STATE codes do not indicate any kind of fault. |
STATE 307 | LOW PV VOLTAGE DC input voltage too low for feeding energy into the grid |
||
STATE 308 | Intermediate circuit overvoltage | Short term interruption while feeding energy into the grid. The inverter resumes with its startup routine. | Fault is rectified automatically; if this STATE code is displayed all the time: notify your local Fronius service partner. |
STATE 309 | DC input voltage too high |
Fronius STATE codes beginning with 4xx
Fronius STATE codes beginning with 4 are error states that require the intervention of a Fronius Service Partner. They are either temporary or lasting and are triggered by faulty hardware or a software problem. Try switching off the Fronius inverter following the system shutdown procedure, leave off for a few minutes then attempt to restart. If the fault continues please contact your local Fronius Service Partner for further assistance.
Code |
Description |
Behaviour |
Remedy |
STATE 401 | No communication with power stage set possible | The inverter will automatically attempt to connect again and, if possible, will resume feeding energy into the grid. | If the STATE code is displayed all the time contact your local Fronius Service Partner |
STATE 406 | Power stage set temperature sensor faulty | ||
STATE 407 | Internal temperature sensor faulty | ||
STATE 408 | DC feeding into the grid detected | ||
STATE 412 | Fixed voltage mode has been selected instead of MPP voltage mode and the fixed voltage has been set to too low or too high a value | – | If this STATE code persists contact your solar power system installer |
STATE 415 | Safety cut out via option card or RECERBO has triggered | The inverter is not feeding any energy into the grid. | If the STATE code is displayed all the time contact your local Fronius Service Partner |
STATE 416 | No communication possible between power stage set and control system | The inverter will automatically attempt to reconnect again and, if possible, will resume feeding energy into the grid. | |
STATE 425 | No communication possible with the power stage set | ||
STATE 445 | Invalid limit value settings | The inverter is not feeding any energy into the grid for safety reasons. | Update the inverter firmware with the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner. |
STATE 452 | Communication error between the processors | The inverter will automatically attempt to connect again, and if possible, will resume feeding energy into the grid. | If the STATE code is displayed all the time: notify your local Fronius Service Partner. |
STATE 453 | Short term grid voltage error | ||
STATE 454 | Short term grid frequency error | ||
STATE 457 | Grid relay sticking | The inverter is not feeding any energy into the grid. | Contact your local Fronius Service Partner. |
STATE 459 | Error when recording the measuring signal for the insulation test | ||
STATE 460 | Reference voltage source for the digital signal processor (DSP) is working out of tolerance | ||
STATE 472 | Fuse for solar panel ground is faulty | Replace fuse for solar panel ground; if this STATE code keeps recurring contact your solar power system installer. | |
STATE 475 | Solar panel ground, insulation fault (connection between solar panel and ground) | If this STATE code keeps recurring, contact your solar power system installer | |
STATE 482 | Startup incomplete | Perform AC reset (turn AC circuit breaker off and on), complete startup. |
Fronius STATE codes beginning with 5xx
Fronius STATE codes beginning with 5 generally do not stop the feed in operation of the Fronius Galvo inverter. The STATE codes will be displayed until the message is acknowledged by pushing a button on the display (the inverter will work in feed in operation during this time).
Code |
Description |
Behaviour |
Remedy |
STATE 502 | Insulation error on the solar panels | Warning message is shown on the display | If this STATE code keeps recurring, contact your solar power system installer. |
STATE 509 | No energy fed into the grid in the past 24 hours | It is normal to see the state 509 code when the inverter has just been installed. Acknowledge STATE code; check whether all the conditions for the problem free feeding of energy into the grid have been met. If the STATE code is displayed all the time: look out for further STATE codes. | |
STATE 516 | Firmware fault | Firmware fault with the inverter, firmware update required. | Update the inverter firmware with the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner. |
STATE 517 | Derating caused by too high a temperature | When power derating occurs, a warning message is shown on the display | Purge cooling air openings and heat sink if necessary; fault is rectified automatically; if this STATE code keeps recurring contact your solar power system installer. |
STATE 551 | Fuse for solar panel ground is faulty | Warning is shown on display | Replace fuse for solar panel ground; if this STATE code keeps recurring contact your solar power system installer. |
STATE 558 | Functional incompatibility (one or more PC boards in the inverter are not compatible with each other, e.g. after a PC board has been replaced) | Possible error displays or malfunction on the inverter | If this STATE code keeps recurring contact your solar power system installer. |
STATE 560 | Derating caused by over-frequency | This STATE code is displayed when the grid frequency becomes excessively high. The inverter will then reduce its output. The status indicator will continue to be displayed until the inverter has returned to normal operation. | As soon as the grid frequency is back within the permissible range and the inverter has returned to normal operation, the fault is rectified automatically. If this STATE code keep recurring contact your solar power system installer. |
STATE 567 | Grid Voltage Dependent Power Reduction is active | This state code is a warning informing you that the Grid Voltage Dependent Power Reduction mode (GVDPR or Volt – Watt mode) has been activated and the inverter will continue to operate with reduced power output. This is because the grid voltage has exceeded 250Vac and the GVDPR has been enabled to try to reduce the voltage rise at the inverters terminals. This mode must be enabled by default in accordance with the latest Australian Standards. | Acknowledge status code; if the STATE 567 code keeps recurring contact your local solar power system installer. Find out more about the STATE 567 message here |
STATE 568 | Incorrect input signal on the multifunction current interface | The STATE code is displayed in the case of an incorrect input signal on the multi-function current interface and with the following setting: Basic menu / Input signal / Mode of operation = Ext. Signal, triggering method = Warning | Acknowledge status code; check the devices connected to the multi-function current interface; if this STATE code keeps recurring contact your solar power system installer. |
Fronius STATE codes beginning with 6xx
Some of the class 6 STATE codes necessitate intervention by a Fronius Service Partner.
Code |
Description |
Behaviour |
Remedy |
STATE 668 | Incorrect input signal on the multi-function current interface | The inverter is not feeding any energy into the grid. The STATE code is displayed in the case of an incorrect input signal at the multi-function current interface and with the following setting: Basic menu / Input signal / Mode of operation = Ext. Signal, triggering method = Ext. Stop |
Check the devices connected to the multi-function interface; if this STATE code keeps recurring: notify your local Fronius service partner. |
Fronius STATE codes beginning with 7xx
Class 7 STATE codes on Fronius Galvo inverters relate to the control system, the configuration and inverter data recording, and may directly or indirectly affect the process of feeding energy into the grid.
Code |
Description |
Behaviour |
Remedy |
STATE 705 | Conflict when setting the inverter number (e.g. number already assigned) | – | Correct the inverter number via the setup menu |
STATE 721 | EEPROM has been reinitialised or EEPROM is faulty | Warning message is shown on the display | Acknowledge STATE code; If the STATE code is displayed all the time contact your local Fronius Service Partner |
STATE 731 | Initialisation error – USB stick is not supported | Check or replace USB stick. Check the file system on the USB stick. If the STATE code is displayed all the time notify your local Fronius Service Partner. | |
STATE 732 | Over current on USB stick | ||
STATE 733 | No USB stick connected | Connect or check the USB stick. If STATE code is displayed all the time contact your local Fronius Service Partner. | |
STATE 734 | Update file not recognised or not present | Check update file (e.g. for correct file name). If STATE code is displayed all the time contact your local Fronius Service Partner. | |
STATE 735 | Update file does not match the device, update file too old | Warning message appears on the display, update process is interrupted. | Update the inverter firmware with the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner. |
STATE 736 | Write or read error occurred | Warning message is shown on the display | Check USB stick and the data contained on it or replace USB stick. Never unplug a USB stick if the ‘Data Transmission’ LED is still flashing or lit. If the STATE code is displayed all the contact your local Fronius Service Partner. |
STATE 738 | Log file cannot be saved (e.g. USB stick is write protected or full)t | Create storage space, remove write protection, check or replace USB stick if necessary. If STATE code is displayed all the time contact your local Fronius Service Partner. |
|
STATE 743 | Error occurred during update process | Repeat the update process, check USB stick. If STATE code is displayed all the time contact your local Fronius Service Partner. | |
STATE 745 | Update file corrupt | Warning message appears on the display, update process is interrupted. | Re-download the inverter firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner. |
STATE 751 | Time lost | Warning message is shown on the display | Reset the time and date on the inverter. Check update file (e.g. for correct file name). If STATE code is displayed all the time contact your local Fronius Service Partner. |
STATE 752 | Real Time Clock module communication error | ||
STATE 757 | Hardware error in the Real Time Clock module | Error message is shown on the display; the inverter is not feeding any energy into the grid. | If STATE code is displayed all the time contact your local Fronius Service Partner. |
STATE 758 | Internal error: Real Time Clock module is in emergency mode | Time may be inaccurate or lost (feeding energy into the grid normal).. | |
STATE 766 | Emergency power de-rating has been activated | Error message is shown on the display. |
Fronius is an Austrian manufacturer of solar inverters and are well known for their quality and fast response to warranty claims. If you are on the Gold Coast or South Brisbane and your Fronius Galvo inverter is giving you problems then contact us here or give us a call on 07 55 228 980 – we are here to help ensure that your solar power system remains an asset rather than a liability!