IMEON Smart Grid Hybrid Solar Inverter   IMEON Smart Grid Hybrid Solar Inverter

IMEON Smart Grid Hybrid Solar Inverter came onto the market as an all in one solution for the installation of a self consumption solar system. It was designed to enable you to become power self sufficient, even in the case of power blackouts.

The inverters come with the following warranty guarantees:

  • Standard 5 year warranty for units not connected to the internet.
  • 10 year warranty if the unit is connected to the internet (the connection must be established for minimum of 95% of operating time).
  • There is an option to increase this to 20 years.

IMEON Energy is a French company which began producing solar inverters in 2013.

If your IMEON Smart Grid Hybrid inverter is showing a fault message, the first step is to reboot your system. The following is the shut down and startup procedure recommended by IMEON:

Shutdown the inverter
1- Switch all protective devices to OFF position in the following order.
1. PV switch
2. Battery switch
3. AC breakers
2- Wait for the LCD display of the inverter to shut down (maximum 30sec).

Restart the inverter
1- Switch all protective devices to ON position in the following order.
1. AC breakers
2. Battery switch
3. PV switch

IMEON data sheet and user manual

IMEON Data Sheet
IMEON user manual

For convenience, we have put together a list of error messages, possible causes and remedies. If you are not very keen in performing the procedures below, we recommend that you contact a qualified electrician to avoid any injury, data loss or system crash.

Code Type Description
2 warning_ond Islanding detected. If this problem remains, please contact your grid operator
3 warning_ond Grid voltage higher than the limit of the norm. If this problem remains, please contact your
grid operator.
4 warning_ond Grid voltage lower than the limit of the norm. If this problem remains, please contact your
grid operator.
5 warning_ond Grid frequency higher than the limit of the norm. If this problem remains, please contact your
grid operator
6 warning_ond Grid frequency lower than the limit of the norm. If this problem remains, please contact your
grid operator
7 warning_ond Grid voltage lost. Check if the GRID CONNECTION connector is correctly supplied by the
public grid. If this problem remains, please contact your grid operator.
9 warning_ond Grid frequency lost. Check if the GRID CONNECTION connector is correctly supplied by the
public grid. If this problem remains, please contact your grid operator.
10 warning_ond There is a phase rotation problem. Reverse 2 phases and restart the inverter
11 warning_ond Grid sinus lost. Check if the GRID CONNECTION connector is correctly supplied by the
public grid. If this problem remains, please contact your grid operator.
12 warning_ond Average grid voltage greater than norm voltage for 10 min. If this problem remains, please
contact your grid operator
13 warning_ond Overload on the AC BACKUP. Remove the high power devices with inrush power (air
conditioner, pumps,…).
14 warning_ond High inverter temperature. Please check the good ventilation of your inverter and the
temperature in the inverter room.
15 warning_ond Earth default. Please check inverter is correctly connected to the ground
22 warning_pv Low PV2 voltage. Check the PV sizing, connection and installation
23 warning_pv PV voltage too high. Check the PV sizing and installation. This problem can cause a critical
electronic damage
24 warning_pv PV2 voltage too high. Check the PV sizing and installation. This problem can cause a critical
electronic damage.
25 warning_cpu CPU1 flash failure. Please reboot the inverter and check the version is the last one. If the
problem remains, please contact your distributor.
26 warning_cpu CPU1 start failure. Please reboot the inverter and check the version is the last one. If the
problem remains, please contact your distributor
27 warning_bat Battery warning reported. Check the battery ID warning in IMEON OS. ONE. If the problem
remains contact your battery distributor
30 warning_bat Battery not connected. Please connect the batteries and check if a breaker/fuse is not open
between inverter and batteries. If the problem remains contact your battery distributor
32 warning_bat Battery voltage too high. Disconnect your battery and check if the battery specifications
comply with inverter
35 error_ond CPU1 communication failure. Please reboot the inverter and check the version is the last
one. If the problem remains, please contact your distributor
37 error_soft Internal wiring failure. Please reboot the inverter. If the problem remains contact your
distributor or IMEON for repair
38 error_soft Software service failure. Please reboot the inverter. If the problem remains, please contact
your distributor
39 error_soft Software service failure. Please reboot the inverter. Please reboot the inverter and check the
version is the last one. If the problem remains, please contact your distributor
40 error_soft Software service failure. Please reboot the inverter. Please reboot the inverter and check the
version is the last one. If the problem remains, please contact your distributor
41 error_soft Software service failure. Please reboot the inverter. Please reboot the inverter and check the
version is the last one. If the problem remains, please contact your distributor
42 error_pv PV overvoltage. This problem may cause a critical electronic damage, stop immediately the
PV production and check the PV sizing and installation. If the problem remains, please
contact your distributor.
43 error_pv PV overcurrent. This problem may cause a critical electronic damage, stop immediately the
PV production and check the PV sizing and installation. If the problem remains, please
contact your distributor.
44 error_pv Solar insulation too low. Measure the PV insulation which must be higher than 600kOhm for
IMEON 3.6 and 1Mohm for IMEON 9.12. If the problem remains, please contact your
distributor.
45 error_ond DC BUS overvoltage. This problem may cause a critical electronic damage. Please reboot
the batteries and the inverter. If the problem remains, please contact your distributor.
46 error_ond DC BUS undervoltage. Please reboot the inverter, activate the AC BACKUP and connect the
battery. If the problem remains, please contact your distributor
47 error_ond DC BUS soft start timeout. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
48 error_ond Inverter circuit soft start timeout. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
49 error_ond Inverter overcurrent. Inverter may have a critical failure as a result of an overload or a short
circuit. Stop immediately the inverter and check the installation. If the problem remains,
please contact your distributor.
50 error_ond Overheating. This problem may cause a critical electronic damage, stop the inverter and
check the good ventilation of inverter and temperature of the room.
51 error_ond Internal relay failure. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor
52 error_ond DC current sensor failure. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
53 error_ond PV overvoltage. This problem may cause a critical electronic damage, stop immediately the
PV production and check the PV sizing and installation. If the problem remains, please
contact your distributor.
54 error_ond Over leakage current. Check that all the devices connected to the installation are wired on a
unique ground system. If the problem remains, please contact your distributor.
55 error_ond DC BUS overcurrent. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor
56 error_ond CPU1 measurement error. Please reboot the inverter and check the version is the last one. If
the problem remains, please contact your distributor
57 error_ond GFCI sensor failure. Please reboot the inverter. If the problem remains, please contact your
distributor.
58 error_ond AC input ground lost. There is an electrical security problem. Please check the inverter earth
connection.
59 error_ond Discharge DC BUS failure. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
60 error_ond Discharge DC BUS soft start timeout. This problem may cause a critical electronic damage.
Stop immediately the inverter and check the installation. If the problem remains, please
contact your distributor.
61 error_ond Overload on the AC BACKUP. Remove the high power devices with inrush power. If the
problem remains, please contact your distributor
62 error_ond Overcurrent on the AC BACKUP. Remove the high power devices with inrush power. If the
problem remains, please contact your distributor
63 error_ond AC BACKUP short-circuits. Shutdown the inverter, then unplug the AC BACKUP connector,
then restart the inverter and activate the AC BACKUP by pushing the OK button during 3sec.
If this error is resolved, the issue comes from a connected device on the AC BACKUP
connector. If the problem remains, please contact your distributor
64 error_ond Fan failure. Please restart the inverter. If the problem remains, please contact your
distributor.
65 error_ond AC BACKUP sensor failure. Please restart the inverter. If the problem remains, please
contact your distributor
66 error_ond Hardware version detection error. Please restart the inverter. If the problem remains, please
contact your distributor.
67 error_ond AC Input/Output reversal. This problem may cause a critical electronic damage. Stop the
inverter and check the AC Grid and AC BACKUP connections are not reversed. If the
problem remains, please contact your distributor
68 error_ond AC BACKUP undervoltage. Please reboot the inverter and activate the AC BACKUP. If the
problem remains, please contact your distributor
69 error_ond AC BACKUP overvoltage. Please reboot the inverter and activate the AC BACKUP. If the
problem remains, please contact your distributor
70 error_bat Battery voltage too high. This problem may cause a critical electronic damage. Disconnect
your battery and check if its specifications comply with inverter. If the problem remains,
please contact your battery distributor.
71 error_bat Battery not connected. Please connect the batteries and check if a breaker/fuse is not open
between inverter and batteries. If the problem remains contact your battery distributor.
72 error_bat Charging current error. Check battery settings and check the battery connection & voltage. If
the problem remains, please contact your distributor
73 error_bat Battery voltage differs from communicated value. There is a communication problem
between inverter and battery BMS. Please reboot the battery and inverter and check the
good connection of battery communication cable. If the problem remains, please contact
your distributor.
74 error_ond Internal supply failure. Please restart the inverter. If the problem remains, please contact
your distributor.
75 com_lost CAN communication lost. There is a communication problem between inverter and battery
BMS. Please reboot the battery and inverter and check the good connection of battery
communication cable. If the problem remains, please contact your distributor.
76 error_bat Battery error reported. Check the battery ID error in OS. ONE, then restart the battery and
the inverter. If the problem remains contact your battery distributor.
77 com_lost Communication lost between processors. Please reboot the inverter. If the problem remains,
please contact your distributor.
78 com_lost Internet connection lost. Check your internet connection.
87 error_bat Battery current exceeds max battery current limit. Please check the good setting of battery
parameter in OS. ONE. If the problem remains contact your battery distributor.
88 error_ond Power on grid connection overpasses maximum power specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
89 error_ond Current on grid connection overpasses maximum power specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
90 error_ond Frequency on AC BACKUP exceeds minimum frequency specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
91 error_ond Frequency on AC BACKUP exceeds maximum frequency specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor
92 error_ond Current on AC BACKUP overpasses maximum current specification. Remove the high
power devices with inrush power (air conditioner, pumps,…). This problem can cause a
critical electronic damage. If the problem remains contact your distributor
93 error_ond PV input power overpasses specification. This problem can cause a critical electronic
damage. Please check the PV sizing, connection and installation. If the problem remains
contact your distributor.
94 error_ond PV2 input power overpasses specification. This problem can cause a critical electronic
damage. Please check the PV sizing, connection and installation. If the problem remains
contact your distributor
95 error_ond Temperature exceeds the specification of the inverter. Please check the installation, this
problem can cause a critical electronic damage. If the problem remains contact your
distributor.
96 error_ond Battery discharging current overpasses specification of the inverter. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
97 com_lost Communication lost between Inverter and Smartmeter. Please check the wiring between
Smartmeter and inverter. If the problem remains, contact your distributor.
98 error_spe Voltage on grid connection exceeds minimum voltage specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
99 error_spe Voltage on grid connection exceeds maximum voltage specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
100 error_spe Frequency on grid connection exceeds minimum frequency specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
101 error_spe Frequency on grid connection exceeds maximum frequency specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
102 error_spe Voltage on AC BACKUP exceeds minimum voltage specification.
Please check the installation, this problem can cause a critical electronic damage. If the
problem remains contact your distributor.
103 error_spe Voltage on AC BACKUP exceeds maximum voltage specification.
Please check the installation, this problem can cause a critical electronic damage. If the
problem remains contact your distributor.
104 error_spe Power on AC BACKUP overpasses maximum power specification. Remove the high power
devices with inrush power. This problem can cause a critical electronic damage. If the
problem remains contact your distributor.
105 error_spe Voltage on DC bus overpasses maximum voltage specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
106 error_spe Voltage on Battery overpasses maximum voltage specification. Disconnect the battery and
check the voltage on terminal complies with inverter specifications. If the problem remains
contact your distributor
107 error_spe PV input current overpasses specification. Stop the PV production and check the PV sizing,
connection and installation. If the problem remains contact your distributor.
108 error_spe PV2 input current overpasses specification. Stop the PV production and check the PV sizing,
connection and installation. If the problem remains contact your distributor.
109 error_spe PV input voltage overpasses specification. Stop the PV production and check the PV sizing,
connection and installation. If the problem remains contact your distributor.
110 error_spe PV2 input voltage overpasses specification. Stop the PV production and check the PV
sizing, connection and installation. If the problem remains contact your distributor.
111 error_spe Battery charging current overpasses specification of the inverter. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
112 error_ond Neutral / Ground wires reversed. Stop the inverter and check the Neutral and Ground wires
are not reversed on “GRID CONNECTION” connector and “AC BACKUP” connector. If the
problem remains contact your distributor

If you need more information, the full details are available in the IMEON Solar Inverter manual’s Troubleshooting section.  Check if your IMEON Solar Inverter is still within the warranty period so you can contact the equipment installer or supplier for repair if the error continues.  If your IMEON Hybrid inverter is outside the warranty period we suggest that you contact a professional solar power expert. If you’re in the Gold Coast or Brisbane area, contact Gold Coast Power Solutions and we will be in touch to provide you with further assistance.