Ingeteam Solar Inverters Ingeteam Solar Inverters, data sheets, user manuals & errors

Ingeteam have been designing and manufacturing Solar Inverters for over 16 years. Ingeteam is a Spanish company and their headquarters in is Pamploma, Spain, although they do have an office in Australia. They manufacture a range of inverters from residential and commercial to solar farm inverters.

Residential inverter models are

  • INGECON SUN 1Play – 2.5kW to 6 kW in size (single phase)
  • INGECON SUN 3Play – 10kW – 33kW in size (three phase)

The Ingeteam INGECON SUN 1Play and SUN 1Play inverters come with the standard 5 year warranty.

If your Ingeteam inverter is showing a fault message, the first step is to reboot your system.

Ingeteam inverter data sheets and user manuals

Ingeteam INGECON SUN 1Play datasheet
Ingeteam INGECON SUN 3Play datasheet

For convenience, we have put together a list of error messages, possible causes and remedies. If you are not very keen in performing the procedures below, we recommend that you contact a qualified electrician to avoid any injury, data loss or system crash.

Faults and errors for Ingeteam INGECON SUN 1Play inverter

Alarm LED Lighting*
number of flashes shown
Description Solution
Vdc1 overvoltage Orange, 6 Overvoltage in DC input number 1 Check the connections of the PV array, ensuring the
series-parallel configuration of the panels is correct,
and that the maximum voltage of the inverter has
not been exceeded
Vdc2 overvoltage Orange, 6 Overvoltage in DC input number 2
Idc1 overcurrent Red, 1 Overcurrent in DC input number 1 Check the installation in the DC part.

If the error persists, contact the Technical Service.

Idc2 overcurrent Red, 1 Overcurrent in DC input number 2
Vbus overvoltage Red,2 Overvoltage in the bus Check the connections of the PV array, ensuring the
series-parallel configuration of the panels is correct,
and that the maximum voltage of the inverter has
not been exceeded.
Inst. Overvolt. Vac Orange, 2 Instantaneous overvoltage at the
AC output
Check the connections of the AC side. Check that
the voltage of the electricity grid is within range.
Vac out of range Orange, 2 AC output voltage out of the
defined range
Inst. Overcurr. Iac Red, 1 Instantaneous overcurrent at the
AC output
Check the installation in the AC part.
If the error persists, contact the Technical Service.
Iac out of range Red, 1 AC output current out of the
defined range
Fac out of range Orange, 3 AC grid frequency out of the
defined range
Check the connections of the AC side. Check that
the frequency of the electricity grid is within range.
DC/DC pwm fault Red, 3 Firmware fault in the DC/DC phase Check the installation in the DC and AC part.

If the error persists, contact the Technical Service.

DC/AC pwm fault Red, 3 Firmware fault in the DC/AC
conversion phase
DC/DC hw fault Red, 3 Hardware fault in the DC/DC
phase
DC/AC hw fault Red, 3 HW fault in the DC/AC conversion
phase
Temperature alarm Orange, 4 Temperature out of operating
range
This may be normal if the room temperature
exceeds the maximum of the unit. Check the
functioning of the fans. Protect the inverter from
direct exposure to sunlight. Cool the room where the
inverter is installed.
Manual stop Orange, constant The inverter has been manually
stopped.
Start the inverter by means of the display.
Hardware error Red, 1 The inverter displays a hardware
error
Disconnect the DC and AC inverter. Wait until the
LEDs go off and re-connect. If the problem persists,
contact the Technical Service.
Residual current Orange, 5 Residual current out of range Check that there are no insulation faults in the PV
array. Check that the stray capacity of the PV array
does not exceed the maximum permitted.
FW update Orange, constant Inverter shutdown due to firmware
load
Normal shutdown due to inverter firmware update.
Grid consumption Orange, 1 Grid consumption power out of the
permitted range
This may be due to a low irradiance level. Otherwise,
check the PV array.
Low pow. PV conn. Orange, 1 The generated power in the PV
array is not sufficient to connect to
the AC grid
Config. change Red, 1 Inverter setting change Normal shut down due to a change in the inverter
setting.
Isolation alarm Orange, 5 Insulation resistance out of range Check, on the display, that the PV array grounding is
correctly configured. Search for an insulation fault in
the PV array. If one of the poles is grounded, check
the grounding fuse.
Satur. alarm Iac Orange, 5 AC current saturation Check the installation in the AC part.
If the error persists, contact the Technical Service
Low Vdc Orange, 1 Low DC voltage This may be due to a low irradiance level. Otherwise,
check the PV array.
Blocked fan Orange, 7 Possible fan blockage Check the condition of the fan and that there are no
elements that prevent it functioning properly.
High temperature Orange, 7 Power regulation due to
temperature above operating
temperature
Check the room temperature does not exceed the
specified maximum temperature and the inverter
is not exposed to direct sunlight. Also check the
functioning of the fans.
Low temperature Orange, 7 Temperature below operating
temperature
Check the room temperature is not below the
specified minimum temperature.
Self-cons. commun. Orange, 7 Communication fault with the self
consumption devices (wattmeter
or INGECON EMS Manager)
Check the connection of the different elements. If
the error persists, contact the Technical Service.

Faults and errors for Ingeteam INGECON SUN 3Play inverter

Alarm LED Lighting
number of flashes shown
Description Solution
Vdc1 overvoltage Orange, 6 Overvoltage in DC input number 1 Check the connections of the PV array, ensuring the
series-parallel configuration of the panels is correct,
and that the maximum voltage of the inverter has
not been exceeded
Vdc2 overvoltage Orange, 6 Overvoltage in DC input number 2
Idc1 overcurrent Red, 1 Overcurrent in DC input number 1 Check the installation in the DC part.

If the error persists, contact the Technical Service.

Idc2 overcurrent Red, 1 Overcurrent in DC input number 2
Vbus overvoltage Red, 2 Overvoltage in the bus Check the connections of the PV array, ensuring the
series-parallel configuration of the panels is correct,
and that the maximum voltage of the inverter has
not been exceeded.
Inst. Overvolt. Vac Orange, 2 Instantaneous overvoltage at the
AC output
Check the connections of the AC side. Check that
the voltage of the electricity grid is within range.
Vac out of range Orange, 2 AC output voltage out of the
defined range
Inst. Overcurr. Iac Red, 1 Instantaneous overcurrent at the
AC output
Check the installation in the AC part.
If the error persists, contact the Technical Service.
Iac out of range Red, 1 AC output current out of the
defined range
Fac out of range Orange, 3 AC grid frequency out of the
defined range
Check the connections of the AC side. Check that
the frequency of the electricity grid is within range.
DC/DC pwm fault Red, 3 Firmware fault in the DC/DC phase Check the installation in the DC and AC part.

If the error persists, contact the Technical Service.

DC/AC pwm fault Red, 3 Firmware fault in the DC/AC
conversion phase
DC/DC hw fault Red, 3 Hardware fault in the DC/DC
phase
DC/AC hw fault Red, 3 HW fault in the DC/AC conversion
phase
Temperature alarm Orange, 4 Temperature out of operating
range
This may be normal if the room temperature
exceeds the maximum of the unit. Check the
functioning of the fans. Protect the inverter from
direct exposure to sunlight. Cool the room where the
inverter is installed.
Fatal error Red, constant Fatal error Disconnect the DC and AC inverter. Wait until the
LEDs go off and re-connect. If the problem persists,
contact the Technical Service.
Manual stop Orange, constant The inverter has been manually
stopped.
Start the inverter by means of the display.
Hardware error Red, 1 The inverter displays a hardware
error
Disconnect the DC and AC inverter. Wait until the
LEDs go off and re-connect. If the problem persists,
contact the Technical Service.
Residual current Orange, 5 Residual current out of range Check that there are no insulation faults in the PV
array. Check that the stray capacity of the PV array
does not exceed the maximum permitted.
FW update Orange, constant Inverter shutdown due to firmware
load
Normal shutdown due to inverter firmware update.
Grid consumption Orange, 1 Grid consumption power out of the
permitted range
This may be due to a low irradiance level. Otherwise,
check the PV array.
Low pow. PV conn. Orange, 1 The generated power in the PV
array is not sufficient to connect to
the AC grid
Power supply fault Red, 1 Fault in power supply to the
electronic circuit boards
Check the correct connection of the DC cables.
Open the unit and check the correct connection of
the control board.
Idc grid injection Red, 3 DC current fed to the grid out of
the permitted range
Check the installation in the AC part.

If the error persists, contact the Technical Service

Config. change Red, 1 Inverter setting change Normal shut down due to a change in the inverter
setting.
Isolation alarm Orange, 5 Insulation resistance out of range Check, on the display, that the PV array grounding is
correctly configured. Search for an insulation fault in
the PV array. If one of the poles is grounded, check
the grounding fuse.
Satur. alarm Iac Orange, 5 AC current saturation Check the installation in the AC part.
If the error persists, contact the Technical Service
Low Vdc Orange, 1 Low DC voltage This may be due to a low irradiance level. Otherwise,
check the PV array.
Blocked fan Orange, 7 Possible fan blockage Check the condition of the fan and that there are no
elements that prevent it functioning properly.
High temperature Orange, 7 Power regulation due to
temperature above operating
temperature
Check the room temperature does not exceed the
specified maximum temperature and the inverter
is not exposed to direct sunlight. Also check the
functioning of the fans.
Low temperature Orange, 7 Temperature below operating
temperature
Check the room temperature is not below the
specified minimum temperature.
High Vdc Orange, 7 High DC input voltage Check the connections of the PV array, ensuring the
series-parallel configuration of the panels is correct,
and that the maximum voltage of the MPP has not
been exceeded.
String kit comm. Orange, 7 Communication failure with strings
reading card (only in versions P
and P+)
Contact technical service.
Self-cons. commun. Orange, 7 Communication fault with the self
consumption devices (wattmeter
or INGECON EMS Manager)
Check the connection of the different elements. If
the error persists, contact the Technical Service.
Surge arrester error Orange, 7 Fault in DC arresters Check the condition of the surge arresters and
replace as required.

If you need more information, the full details are available in the Ingeteam INGECON SUN 1Play and SUN 3Play Solar Inverter manual’s Troubleshooting section.  Check if your Ingeteam Solar Inverter is still within the warranty period so you can contact the equipment installer or supplier for repair if the error continues.  If your Ingeteam inverter is outside the warranty period we suggest that you contact a professional solar power expert. If you’re in the Gold Coast or Brisbane area, contact Gold Coast Power Solutions and we will be in touch to provide you with further assistance.

 

 

 