Huawei SUN2000L Solar Inverters

Huawei SUN2000L Solar Inverters

Huawei entered the solar inverter market in 2013. Huawei sold mainly to China and the wider Asian and European markets and are relatively unknown in Australia.

The Huawei SUN2000L inverter range (2 – 5kW) are compact and have the ability to function as a stand alone string inverter with partial or full panel optimisation. The SUN2000L  inverters have a built-in DC coupling battery interface which is compatible with LG Chem RESUH batteries. Please note that it does not have Emergency Power Supply so in the event of a blackout your lights will not stay on.

Huawei SUN2000L inverters come with a standard 5 year warranty

If you experience an issue on a Huawei Solar Inverter, the manual shutdown procedure is useful in fixing some errors. There are also other faults that require other procedures.

Huawei Solar Inverter data sheet

Huawei data sheet

For convenience, we have put together a list of error messages, possible causes and remedies.

Alarm severities are defined as follows:

  • Major: The SUN2000L enters Shutdown mode and disconnects from the power grid to stop generating power after a fault occurs.
  • Minor: Some components are faulty but the SUN2000L can still connect to the power grid and generate power.
  • Warning: The SUN2000L output power decreases due to external factors.
Alarm ID Alarm Name Alarm
Severity
Possible Cause Suggestion
2001 High String Input
Voltage
Major The PV array is incorrectly configured. Excessive PV modules are connected in series to the PV string, and
therefore the open-circuit voltage exceeds the maximum inverter input voltage.
Reduce the number of PV modules connected in series to the PV string until the PV string open-circuit voltage is less than or equal to the maximum inverter input voltage.
After the PV array is correctly
configured, the inverter alarm
disappears.
The following is the mapping
between PV strings and alarm cause
IDs:
– Cause ID 1: string 1
– Cause ID 2: string 2
Contact your installer
2011 String Reversed Major The PV string is reversely
connected.
Check whether the PV string is
reversely connected to the
SUN2000L. If so, wait until the solar irradiance declines at night and the PV string current reduces to below 0.5 A. Then, turn off the DC switch and correct the PV string polarity.
The following is the mapping
between PV strings and alarm cause
IDs:
– Cause ID 1: string 1
– Cause ID 2: string 2
Contact your installer
2032 Grid Failure Major Cause ID = 1
– The power grid experiences an outage.
– The AC circuit is
disconnected or AC switch is off.
1. Check the AC voltage.

2. Check that the AC power cable is connected and that the AC switch is ON.

2033 Grid Undervoltage Major Cause ID = 1
The grid voltage is below the lower threshold or the low voltage duration has lasted for more than the value specified by LVRT.
1. If the alarm occurs accidentally, the power grid may be abnormal temporarily. The SUN2000L automatically recovers after detecting that the power grid becomes normal.

2. If the alarm occurs frequently,
check whether the grid voltage is
within the acceptable range. If
not, contact the local power
operator. If so, modify the power
grid overvoltage and
undervoltage protection
thresholds with the consent of the local power operator.

3. If the fault persists for a long
time, check the connection
between the AC switch and the
output power cable.

2034 Grid Overvoltage Major Cause ID = 1
The grid voltage exceeds the higher threshold or the high voltage duration has lasted for more than the value specified by HVRT.
1. Check whether the grid
connection voltage exceeds the
upper threshold. If so, contact the local power operator.2. If you have confirmed that the
grid connection voltage exceeds
the upper threshold and obtained the consent of the local power operator, modify the overvoltage and undervoltage protection thresholds.3. Check whether the peak grid
voltage exceeds the upper
threshold.
2035 Grid Overfrequency Major Cause ID = 1
Power grid exception: The actual grid frequency is higher than the local power grid standard.
1. If the alarm occurs accidentally, the power grid may be abnormal temporarily. The SUN2000L automatically recovers after detecting that the power grid becomes normal.

2. If the alarm occurs frequently,
check whether the grid frequency
is within the acceptable range. If
not, contact the local power
operator. If so, modify the grid
overfrequency protection
threshold with the consent of the
local power operator.

2037 Unstable Grid
Frequency
Major Cause ID = 1
Power grid exception: The actual grid frequency change rate does not comply with the local power grid standard.
1. If the alarm occurs accidentally, the power grid may be abnormal temporarily. The SUN2000L automatically recovers after detecting that the power grid becomes normal.

2. If the alarm occurs frequently,
check whether the grid frequency
is within the acceptable range. If
not, contact the local power
operator.

2039 Output
Overcurrent
Major Cause ID = 1
The grid voltage drops
dramatically or the power grid is short-circuited. As a result,
the inverter transient output current exceeds the upper threshold and therefore the inverter protection is triggered.
1. The SUN2000L monitors its
external working conditions in
real time. The SUN2000L
automatically recovers after the
fault is rectified.2. If the alarm occurs frequently and affects the power production of the PV plant, check whether the output is short-circuited. If the fault persists, contact your
supplier.
2040 Output DC
Component
Overhigh
Major Cause ID = 1
The DC component of the SUN2000L output current exceeds the specified upper
threshold.
1. The SUN2000L monitors its
external working conditions in
real time. The SUN2000L
automatically recovers after the
fault is rectified.2. If the alarm occurs frequently,
contact your supplier.
2051 Abnormal
Residual Current
Major Cause ID = 1
The insulation impedance of the input side to PE decreases
when the SUN2000L is
operating
1. If the alarm occurs accidentally, the external power cable may be abnormal temporarily. The SUN2000L automatically recovers after the fault is rectified.

2. If the alarm occurs frequently or persists, check whether the
impedance between the PV string and ground is below the lower threshold.

2061 Abnormal
Grounding
Major Cause ID = 1
– The PE cable for the
SUN2000L is not
connected.
– The voltage between the SUN2000L neutral wire and ground exceeds the upper threshold.
1. Check that the PE cable for the
SUN2000L is connected
properly.2. Check that the voltage between the SUN2000L neutral wire and
ground is within the normal
range. If an isolation transformer is connected, set OFF due to abnormal grounding to Disable by referring to 7.4.5.3 Feature Parameters.
2062 Low Insulation
Resistance
Major Cause ID = 1
– The PV string is
short-circuited to PE.
– The PV string is installed in a moist environment for a long time.
1. Check the impedance between
the PV array output and PE, and
eliminate short circuits and poor
insulation points.2. Check that the SUN2000L PE
cable is correctly connected.3. If you confirm that the impedance is less than the default value in a cloudy or rainy environment, reset Insulation resistance protection.
2063 Overtemperature Major Cause ID = 1
– The SUN2000L is installed in a place with poor ventilation.
– The ambient temperature exceeds the upper threshold.
– The SUN2000L is not
working properly.
1. Check the ventilation and
ambient temperature at the
SUN2000L installation position.2. If the ventilation is poor or the
ambient temperature exceeds the upper threshold, improve the
ventilation and heat dissipation.3. If both the ventilation and
ambient temperature meet
requirements, contact your
supplier.
2064 Device Fault Major Cause ID = 1–12
An unrecoverable fault occurs on a circuit inside the SUN2000L.
Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. If the fault persists, contact your supplier.
2065 Upgrade Failed Major Cause ID = 1–4
The upgrade does not end normally.
1. Perform an upgrade again.

2. If the upgrade fails several times, contact your supplier.

3. Check that the DC power supply is connected.

61440 Monitoring Unit
Faulty
Minor Cause ID = 1
The communication module is faulty.
Contact your supplier to rectify the fault.
2067 Faulty Power
Collector
Major Cause ID = 1
– In Grid Connection with Zero Power mode, the energy meter
communication is
interrupted.
– In Maximum Use of
Self-Produced Power mode, the energy meter
communication is
interrupted.
1. Check that the preset energy
meter model is the same as the
actual model.2. Check that the preset
communications parameters for
the energy meter are the same as
the actual configurations.3. Check that the energy meter is
powered on and the RS485
communications cable is
correctly connected.
2068 Battery Abnormal Minor Cause ID = 1
– The battery is faulty.
– The battery communication
is interrupted.
– The battery switch trips
when the SUN2000L is
running.
1. Check that the communications
cable and power cable between
the SUN2000L and the battery
are properly connected.2. Check that the battery switch is turned on properly.3. Turn off the AC output switch,
DC input switch, and battery
switch, and then turn them on
after 5 minutes. If the fault
persists, contact your supplier.
2075 Peripheral Port Short Circuit Warning Cause ID = 1
The SUN2000L Alarm port is short-circuited when supplying 12 V power to peripheral.
1. Turn off the AC and DC switches on the SUN2000L and disconnect the peripheral from the Alarm port. Then power on the SUN2000L again and clear the alarm manually. If the alarm
persists, contact your supplier to
rectify the fault. If the alarm is
cleared, it indicates that the port
on the SUN2000L is normal.
Then check that the pins in the
power port on the peripheral are
not short-circuited.2. Replace the peripheral, and then start a self-check to check that the port functions properly.

If you need more information, the full details are available in the Huawei Solar Inverter manual’s Troubleshooting section.  Check if your Huawei Solar Inverter is still within the warranty period so you can contact the equipment installer or supplier for repair if the error continues.  If your inverter is outside the warranty period we suggest that you contact a professional solar power expert. If you’re in the Gold Coast or Brisbane area, contact Gold Coast Power Solutions and we will be in touch to provide you with further assistance.

 