ABB / Power One Aurora Riso Low Errors – what can you do?
Have you just walked past your ABB or Power One Aurora solar inverter and been greeted with a Riso Low fault on the screen and a red GFI light?
What does the Riso Low Error mean?
According to the ABB / Power One Aurora operators manual Riso Low indicates the inverter has detected low insulation resistance on the DC side of your solar power system; this is usually not an issue with the inverter but with the DC circuit connected to the inverter. This could be an issue with the cabling, with the DC isolators or with the solar panels.
ABB / Power One Aurora Inverter Riso Low Fault – What To Do
If your ABB / Power One Aurora inverter is showing a Riso Low Fault as mentioned above it’s usually an insulation resistance fault on the DC side. This is an issue which is going to require the expertise of a local solar power expert – if you’re near the Gold Coast or Brisbane area please contact us here.
If you have 2 Solar DC Isolators at the Inverter try this
One thing you can try if you have 2 solar DC isolators beside your inverter is try turning off one of the isolators to isolate the fault. It is possible that the insulation resistance problem your inverter is seeing is just on 1 of the inputs into your inverter so you may be able to isolate the problem and get your solar power system working temporarily on half power. To try this do the following if your have 2 Solar DC Isolators beside your inverter:
- Turn the Solar Supply Main Switch OFF
- Turn both Solar DC Isolators OFF
- Wait for the inverter screen to go blank
- Turn 1 of the Solar DC Isolators back ON
- Turn the Solar Supply Main Switch back ON
- See if the inverter starts up without a fault.
- If the inverter starts up with the Riso Low fault again try repeating steps 1 to 6 but on step 4 turn ON the other Solar DC Isolator.
- If the inverter has started up without the Riso Low error then you have isolated the fault to the Solar DC input which is turned OFF, you still will require a solar power expert to get your solar power system fully operational again.
If the Riso Low error continues then it looks like you will require the assistance of a professional solar power accredited electrician. If you’re near the Gold Coast or Brisbane areas then please fill in your details on the form on this page or contact us here.
Need more information on the ABB / Power-One solar inverters? Checkout the below.
For more information on the ABB/Power-One solar inverters including inverter datasheets, manuals, fault codes etc. click here.
Got A Question About Solar Power? Click Here For Answers!
Hi Tony, the Riso Low error on a Power-One Aurora or ABB inverter signifies a low resistance to earth issue on the DC side or solar panels side of the inverter. If this issue is a consistent fault it isn’t a bad idea to turn the system off. The RISO low error will not affect anything on the AC side of your property so you can still use your power as usual until you can get someone to rectify the issue for you.
My Aurora system is showing Riso low error is it ok
To still use the power until a qualified electrician
Has a look at it or do I need to switch the solar system
Off
Hi Keen, it sounds like you have an issue with the second string of your system then. You will need the assistance of a local solar electrician to rectify the RISO low error on your Aurora inverter.
Dear Simon and team
I hit the same ‘Riso low’ error on my Aurora, which has two DC Isolators.
But it is strange that it can work normally with turning on one of DC Isolator.
When I turn on both two DC Isolators, the ‘Riso low’ error will reproduce.
Please kindly help advise how to fix this issue?
Thank you so much in advance.
Kind Regards
Keen
Hi Des I believe it’s if the resistance is below 1 Meg Ohm with the ABB / Power One Aurora inverters. Thanks